An issue was discovered in Advantech WebAccess Version 8.1. To be able to exploit the SQL injection vulnerability, an attacker must supply malformed input to the WebAccess software. Successful attack could result in administrative access to the application and its data files.
Monthly Archives: February 2017
CVE-2017-5139
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. Any user is able to disclose a password by accessing a specific URL, because of Plaintext Storage of a Password.
CVE-2017-5155
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well.
CVE-2017-5162
An issue was discovered in BINOM3 Universal Multifunctional Electric Power Quality Meter. Lack of authentication for remote service gives access to application set up and configuration.
CVE-2017-5157
An issue was discovered in Schneider Electric homeLYnk Controller, LSS100100, all versions prior to V1.5.0. The homeLYnk controller is susceptible to a cross-site scripting attack. User inputs can be manipulated to cause execution of JavaScript code.
CVE-2016-9371
An issue was discovered in Moxa NPort 5110 versions prior to 2.6, NPort 5130/5150 Series versions prior to 3.6, NPort 5200 Series versions prior to 2.8, NPort 5400 Series versions prior to 3.11, NPort 5600 Series versions prior to 3.7, NPort 5100A Series & NPort P5150A versions prior to 1.3, NPort 5200A Series versions prior to 1.3, NPort 5150AI-M12 Series versions prior to 1.2, NPort 5250AI-M12 Series versions prior to 1.2, NPort 5450AI-M12 Series versions prior to 1.2, NPort 5600-8-DT Series versions prior to 2.4, NPort 5600-8-DTL Series versions prior to 2.4, NPort 6×50 Series versions prior to 1.13.11, NPort IA5450A versions prior to v1.4. User-controlled input is not neutralized before being output to web page (CROSS-SITE SCRIPTING).
CVE-2017-5159
An issue was discovered on Phoenix Contact mGuard devices that have been updated to Version 8.4.0. When updating an mGuard device to Version 8.4.0 via the update-upload facility, the update will succeed, but it will reset the password of the admin user to its default value.
CVE-2017-5161
An issue was discovered in Sielco Sistemi Winlog Lite SCADA Software, versions prior to Version 3.02.01, and Winlog Pro SCADA Software, versions prior to Version 3.02.01. An uncontrolled search path element (DLL Hijacking) vulnerability has been identified. Exploitation of this vulnerability could give an attacker access to the system with the same level of privilege as the application that utilizes the malicious DLL.
CVE-2017-5141
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. An attacker can establish a new user session, without invalidating any existing session identifier, which gives the opportunity to steal authenticated sessions (SESSION FIXATION).
CVE-2017-5169
An issue was discovered in Hanwha Techwin Smart Security Manager Versions 1.5 and prior. Multiple Cross Site Request Forgery vulnerabilities have been identified. The flaws exist within the Redis and Apache Felix Gogo servers that are installed as part of this product. By issuing specific HTTP Post requests, an attacker can gain system level access to a remote shell session. Smart Security Manager Versions 1.5 and prior are affected by these vulnerabilities. These vulnerabilities can allow for remote code execution.